Tutorial
The wall bracing provisions as defined in the 2009 IRC are more complex than those presented in years past. To determine the wall bracing amount a series of calculations must be completed using variables obtained from tables in the IRC. The variables are based on how the home will be constructed, and on its potential exposure to damage. A home that is located in a hurricane-prone or seismically-unstable region, for example, will require longer wall-bracing lengths than a home in an area less prone to natural disaster. Moreover, the taller the structure, the greater its exposure to wind forces and the more bracing it will need.
In an effort to assist Designers with the IRC wall bracing provisions, Simpson Strong-Tie has developed this calculator, which features inputs for all of the variables which are needed to determine the required bracing amount. Please note that while the calculator does simplify the process of determining the required bracing, it is intended for use by an individual who has a firm understanding of the braced wall design provisions of the IRC. The tutorial that follows will guide you through each step of the calculator.
Step 1 – Determine the Seismic Design Category
The seismic design category is a way of measuring the earthquake hazard in a given region. Buildings are assigned a Seismic Design Category (SDC) in accordance with their location on the map shown in IRC Figure R301.2(2). Note the following:
- Buildings in SDC A & B are in the lowest seismic hazard regions and are exempt from the seismic requirements of the IRC, as are detached one- and two-family dwellings in SDC C (see Section R301.2.2). For buildings in these regions this calculator will determine wind bracing amounts only.
- Buildings located in SDC E are in the highest seismic hazard regions and are not permitted to be designed using the IRC. The IRC and this calculator will not evaluate buildings in SDC E (see Section R301.2.2.4).
- The U.S. Geological Survey (USGS) offers a calculation tool to help determine the appropriate Seismic Design Category based on the project site zip code or longitude and latitude. Go to the USGS website at Design Ground Motions (usgs.gov) for more information.
- Contact the local building department to confirm the Seismic Design Category.
Step 2 – Establish the Basic Wind Speed
The Basic Wind Speed is a design parameter that represents a home's potential exposure to a hurricane, as determined by its location on the map in IRC Figure R301.2(4). Note the following:
- This calculator evaluates the wind speeds included in IRC Table R602.10.1.2(1):
85 mph–110 mph. - Buildings located in regions where the basic wind speed equals or exceeds 100 mph in hurricane-prone regions (Atlantic and Gulf of Mexico coasts and several islands) or 110 mph elsewhere may not use the bracing provisions of the IRC (see Section R301.2.1.1). It is the user's responsibility to verify that IRC wind bracing provisions are acceptable where the basic wind speed equals or exceeds 100 mph.
- Contact the local building department to confirm the Basic Wind Speed.
Step 3 – Identify the Wind Exposure Category
The Wind Exposure Category reflects the characteristics of the ground surface surrounding the home. If the home is surrounded by several similar-sized objects, then the wind won't affect it as much as it would if the home were out in the open. The IRC defines the following exposure categories (see Section R301.2.1.4):
- Exposure B: Urban and suburban areas, wooded areas, or other terrain with numerous closely spaced obstructions having the size of single-family dwellings or larger. Exposure B shall be assumed unless the site meets the definition of another type exposure. The wind bracing amounts tabulated in the IRC are based on Exposure B.
- Exposure C: Open terrain with scattered obstructions, including surface undulations or other irregularities, having heights generally less than 30 feet extending more than 1,500 feet from the building site in any quadrant. This exposure shall also apply to any building located within Exposure B- type terrain where the building is directly adjacent to open areas of Exposure C-type terrain in any quadrant for a distance of more than 600 feet. This category includes flat open country, grasslands and shorelines in hurricane-prone regions. Bracing in Exposure C buildings will increase 20-40%.
- Exposure D: Flat, unobstructed areas exposed to wind flowing over open water (excluding shorelines in hurricane-prone regions) for a distance of at least 1 mile. Shorelines in Exposure D include inland waterways, the Great Lakes and coastal areas of California, Oregon, Washington and Alaska. This exposure shall apply only to those buildings and other structures exposed to the wind coming from over the water. Exposure D extends inland from the shoreline a distance of 1,500 feet or 10 times the height of the building or structure, whichever is greater. Buildings in Exposure D will have a 50-70% increase in bracing.
- Contact the local building department with questions about which exposure to assume.
Step 4 – Identify Braced-Wall Lines
Identifying the braced-wall-line design information is probably the single most critical step in developing a bracing plan for the home. This step should be completed by an individual trained in the IRC braced-wall provisions. As such, a detailed explanation of how to identify braced-wall-line information is outside the scope of this tutorial; however, the calculator does require the following definitions inputs:
(Click on the following terms for more information.)
- Number of Parallel Braced-Wall Lines
A minimum of two braced-wall lines are required in a given direction. Additional braced-wall lines will reduce the spacing between braced-wall lines thereby greatly reducing the tabulated wind bracing amounts. To compensate, an adjustment factor must be applied to ensure the total amount of bracing in each direction is about the same for a given structure regardless of the number of braced-wall lines (see Table R602.10.1.2(1) footnote e). The seismic bracing amounts are not affected by the number of parallel braced-wall lines.
- Braced-Wall-Line Spacing
The distance between adjacent, parallel braced-wall lines. The spacing for braced wall lines that have parallel braced-wall lines on both sides is the greater of the distance between each braced-wall line (see Figure R602.10.1.4(4)).
The maximum braced-wall-line spacing for all buildings in SDC A and B and detached one- or two-family dwellings in SDC C is 60 feet (see Table R602.10.1.2(1)). The maximum spacing for townhouses in SDC C is 50 feet (see Table R602.10.1.2(3)). The maximum spacing for all buildings in SDC D0, D1, and D2 is 25 feet with an exception that permits a single spacing up to 35 feet (see Section R602.10.1.5).
This calculator evaluates the parameters entered and limits the maximum spacing to 60, 50, or 35 feet on center and adjusts bracing amounts accordingly. For buildings in SDC D0, D1, and D2 the user must ensure Braced-Wall-Line Spacing greater than 25 feet is acceptable.
- Braced-Wall-Line Location
The required wind and seismic bracing amounts in the IRC are increased as the number of stories above the braced-wall line is increased (see Tables R602.10.1.2(1) and R602.10.1.2(2)).
In some cases the number of stories above the braced-wall lines will be different for braced-wall lines within the same story. One example would be a single-story attached garage that is fully outside the perimeter of a two-story residence.
- Braced-Wall-Line Length
The distance between the ends of the braced-wall line. The end of a braced wall line is considered to be the maximum length resulting from: a) the intersection with perpendicular exterior walls or b) the intersection with perpendicular braced wall lines (see Section R602.10.1).
The longer a braced-wall line, the more mass that wall line must support. Seismic bracing amounts are increased linearly as braced-wall line length is increased. Wind bracing amounts are not affected by braced-wall line length.
- Bracing Method (per wall line)
The building codes define various construction methods that may be used to build a code-compliant braced wall panel:
- Let-In Bracing (LIB)
- Diagonal Wood Board (DWB)
- Wood-Structural-Panel Sheathing (WSP)
- Gypsum Board (GB)
- Structural Fiberboard Sheathing (SFB)
- Particleboard Sheathing (PBS)
- Portland Cement Plaster (PCP)
- Hardboard Panel Siding (HPS)
- Continuously Sheathed (CS)
The required amount of wind and seismic bracing is dependent on the method of wall bracing used. Generally, methods LIB (let-in-bracing) and GB (gypsum board) are considered the weakest, method CS (continuous sheathing) is considered the strongest, and the other methods are in between.
Eight intermittent methods and three narrow alternates are described in Table R602.10.2. Continuous sheathing methods are described in Table R602.10.4.1. Stone or masonry veneer exceeding the 1st story height in higher SDC regions requires wood structural panel sheathing and holdowns installed in accordance with Section R602.12.1.3 and is indicated in this calculator as method BV-WSP.
When mixing bracing methods, the user must ensure the following limits are satisfied (see Section R602.10.1.1):
- Mixing bracing methods from story to story is permitted.
- Mixing intermittent bracing methods from braced-wall line to braced-wall line is permitted.
- Mixing intermittent bracing methods within a single braced-wall line is permitted for all buildings in SDC A and B and detached one- or two-family dwellings in SDC C. The length of required bracing must be based on the highest amount required for each of the methods used in the braced-wall line.
- Mixing continuous sheathing methods and intermittent methods within a single braced wall line is not permitted (see R602.10.4).
- Mixing continuous sheathing methods with intermittent methods from exterior braced wall line to exterior braced-wall line is not permitted in SDC D0, D1, and D2 or in Basic Winds Speeds greater than 100 mph. This is permitted in other regions (see R602.10.4).
Step 5 – Define Other Variables
The final step in using the calculator is to identify miscellaneous variables about the home construction, as follows:
(Click on the following terms for more information.)
- Stone or Masonry Veneer
In some cases, stone or masonry veneer that exceeds the 1st story level will increase the required amount of seismic bracing and/or add new bracing requirements (see Section R602.12). Wind bracing amounts are not affected by stone or masonry veneer. See Section R703.7 for additional information on stone and masonry veneer.
- Eave-to-Ridge Height
Height measured from the top of the wall to the top of the roof ridge. The tabulated bracing amounts in the IRC are based on a height of 10 feet. Increasing or decreasing the height will increase or decrease the wind bracing amounts by as much as -30% to +60% (see Table R602.10.1.2(1) footnote c). The seismic bracing amounts are not affected by the eave-to-ridge height.
- Wall Dead Load
The tabulated seismic bracing amounts in the IRC are based on a 15 psf wall dead load. Dead loads of 8 psf or less will decrease the required seismic bracing amounts by 15% (see Table R602.10.1.2(3)). See Section R301.4 for determining dead loads.
A typical wood-stud partition wall with 1/2-inch gypsum board on both sides has an estimated dead load of 8 psf. A typical exterior wood-stud wall has an estimated dead load greater than 8 psf. See ASCE 7-05 standard and commentary for additional information.
Wind bracing amounts are not affected by wall dead load.
- Roof/Ceiling Dead Load
The tabulated seismic bracing amounts in the IRC are based on a 15 psf Roof/Ceiling Dead Load. Larger dead loads will increase the required seismic bracing amounts up to 20% (see Table R602.10.1.2(3)). See Section R301.4 for determining dead loads.
A typical asphalt shingle roof/ceiling assembly has an estimated dead load of 15 psf or less. Heavier roof coverings such as clay or concrete tile may result in a roof/ceiling dead load greater than 15 psf. See ASCE 7-05 standard and commentary for additional information.
Wind bracing amounts are not affected by roof/ceiling dead load.
- Wall Height
Wall height shall be the vertical distance from the lower edge of the bottom plate to the upper edge of the upper top plate.
As wall height is increased the wind surface area increases and the mass of the wall increases. The tabulated wind and seismic bracing amounts are based on a wall height of 10 feet. Shorter wall heights will reduce the required amount of wind bracing by up to 10%. Taller wall heights will increase the required amount of wind and seismic bracing by up to 20%. See Section R301.3, Table R602.10.1.2(1) footnote d, and Table R602.10.1.2(3) for more information.
- Gypsum Wall Board on Inside
The required wind and seismic bracing amounts are based on braced wall panels with gypsum wall board on the side of the wall opposite the bracing material. Some bracing methods are exempted from this requirement, other methods are permitted to omit the gypsum wall board with increases in bracing amounts up to 80%, and other methods are permitted to omit the gypsum wall board without penalty (see Section R602.10.2.1). This calculator evaluates parameters entered such as bracing method and allows the user to enter yes or no only when permitted. The effect of omitting gypsum wall board is shown as the "Gypsum on Inside Factor" in the Wind and Seismic calculation summary.
- Gypsum Board (GB) Construction Type
The required wind and seismic bracing amounts for Method GB bracing are based on double-sided gypsum wall board. Single-sided gypsum wall board doubles the required bracing amounts (see Table R602.10.1.2(1) footnote g for wind, and Section R602.10.3 for seismic).
Gypsum wall board panels installed horizontally will not require blocking of horizontal joints (see Section R602.10.8) excepted as noted below.
The required wind bracing amount for Method GB may be reduced by 30% when double-sided GB is installed with blocked horizontal joints and fastened at 4 inches on center at all panel edges (see Table R602.10.1.2(1) footnote g).
- Horizontal Joints Blocked
Bracing methods that use sheathing panels must have blocking behind all horizontal joints. Some bracing methods permit the blocking to be omitted when the wind and seismic bracing amounts are doubled, others permit blocking to be omitted without penalty (see Section R602.10.8). This calculator allows the user to enter yes or no only when omitting the blocking is permitted by the bracing method. The effect of omitting blocking is shown as the "Blocked Joint Factor" in the Wind and Seismic calculation summary.
- Holdown Device Used
The required wind bracing amount may be reduced by 20% for some methods when an 800-pound holdown device is used on the end studs of each braced-wall panel in the braced-wall line (see Table R602.10.1.2(1) footnote i).
Stone or masonry veneer exceeding the first-story height in higher SDC regions requires wood structural panel sheathing and holdowns installed in accordance with Section R602.12.1.3 and is indicated in this calculator as method BV-WSP. When method BV-WSP is required, "Holdown Device Used" defaults to "Yes."